The LB-60-80 LOAD BANK is designed to provide a temporary load for field servicing and testing 480VAC and 208VAC three phase, 60HZ generators and inverters. The LB-60-80 load bank is air cooled. A 120VAC outlet is required to operate the fans and relays. The load is 100KW at 480VAC and 80KW at 208VAC. This unit will also test 120VAC & 240VAC single phase.
LB-60-80 DIMENSIONS
Length……………………………..22″ Width…………………………………8″ Height………………………………21″ Weight……………………………..60 lbs. |
LB-60-80 Features
• Load steps: 12.5, 12.5, 25, 25, 25 KW on three phase 480VAC • Load steps: 10, 10, 20, 20, 20 KW on three phase 208VAC • Load steps: 6.5, 6.5, 13, 13, 13 KW on single phase 240VAC • Load steps: 1.6, 1.6, 3.2, 3.2, 3.2 KW on single phase 120VAC • Tests 240VAC three phase, 240VAC single phase and 120VAC single phase • Plug test pins for connecting test leads • Receptacle for 10ft. cable (included with load bank) • Meters: 0-600V voltmeter, 0-250A ammeter, 55-65HZ frequency meter • Power indicator lights • Thermal protection • Carrying case |